PYTHON CONTROL SYSTEMS PROJECT
Off-grid microgrid
dispatch
A 24-hour simulation of how solar, battery storage, and a diesel generator share the load at a remote site.
Unmet load0 kWh
Diesel generation701 kWh
Minimum battery SOC20%
24-HOUR SIMULATION
Dispatch timeline
Solar to loadBattery dischargeDiesel
Battery chargeLoad
Charging is shown below zero. The lower plot tracks battery state of charge (SOC).
SUPERVISORY CONTROL
Control logic
- Serve the load with solar. Send surplus energy to the battery, within its charging limit.
- Use stored energy for deficits. Respect the battery's discharge limit and 20% SOC reserve.
- Dispatch diesel for the remainder. Record unmet demand if all available sources are at their limits.
ACCEPTANCE TESTS
Validation
- Solar surplus charges the battery
- Battery alone covers a small deficit
- Diesel covers the deficit at the SOC floor
- Insufficient capacity records unmet load
- Hourly supply and demand reconcile
Python source
The controller receives demand, available solar, and equipment limits for one hour. It returns battery and diesel energy commands.